Commit 4e57a418 authored by Eric Duminil's avatar Eric Duminil
Browse files

Merge branch 'fix/unstable_calibration' into develop

parents 443cf3bf 925138a8
Pipeline #3627 passed with stage
in 1 minute and 58 seconds
#include "co2_sensor.h"
namespace config {
// Values should be defined in config.h
uint16_t measurement_timestep = MEASUREMENT_TIMESTEP; // [s] Value between 2 and 1800 (range for SCD30 sensor)
const uint16_t measurement_timestep_bootup = 2; // [s] Measurement timestep during acclimatization
// UPPERCASE values should be defined in config.h
uint16_t measurement_timestep = MEASUREMENT_TIMESTEP; // [s] Value between 2 and 1800 (range for SCD30 sensor).
const uint16_t altitude_above_sea_level = ALTITUDE_ABOVE_SEA_LEVEL; // [m]
uint16_t co2_calibration_level = ATMOSPHERIC_CO2_CONCENTRATION; // [ppm]
int8_t max_deviation_during_calibration = 30; // [ppm]
int8_t enough_stable_measurements = 60;
const uint16_t measurement_timestep_bootup = 5; // [s] Measurement timestep during acclimatization.
const uint8_t max_deviation_during_bootup = 20; // [%]
const int8_t max_deviation_during_calibration = 30; // [ppm]
const int16_t timestep_during_calibration = 10; // [s] WARNING: Measurements can be unreliable for timesteps shorter than 10s.
const int8_t stable_measurements_before_calibration = 120 / timestep_during_calibration; // [-] Stable measurements during at least 2 minutes.
#ifdef TEMPERATURE_OFFSET
// Residual heat from CO2 sensor seems to be high enough to change the temperature reading. How much should it be offset?
// NOTE: Sign isn't relevant. The returned temperature will always be shifted down.
......@@ -130,23 +132,26 @@ namespace sensor {
&& co2 < (previous_co2 + config::max_deviation_during_calibration)) {
stable_measurements++;
Serial.print(F("Number of stable measurements : "));
Serial.println(stable_measurements);
Serial.print(stable_measurements);
Serial.print(F(" / "));
Serial.println(config::stable_measurements_before_calibration);
switchState(PREPARE_CALIBRATION_STABLE);
} else {
stable_measurements = 0;
switchState(PREPARE_CALIBRATION_UNSTABLE);
}
previous_co2 = co2;
return (stable_measurements == config::enough_stable_measurements);
return (stable_measurements == config::stable_measurements_before_calibration);
}
void startCalibrationProcess() {
/** From the sensor documentation:
* For best results, the sensor has to be run in a stable environment in continuous mode at
* a measurement rate of 2s for at least two minutes before applying the FRC command and sending the reference value.
* Before applying FRC, SCD30 needs to be operated for 2 minutes with the desired measurement period in continuous mode.
*/
Serial.println(F("Setting SCD30 timestep to 2s, prior to calibration."));
scd30.setMeasurementInterval(2); // [s] The change will only take effect after next measurement.
Serial.print(F("Setting SCD30 timestep to "));
Serial.print(config::timestep_during_calibration);
Serial.println(F("s, prior to calibration."));
scd30.setMeasurementInterval(config::timestep_during_calibration); // [s] The change will only take effect after next measurement.
Serial.println(F("Waiting until the measurements are stable for at least 2 minutes."));
Serial.println(F("It could take a very long time."));
switchState(PREPARE_CALIBRATION_UNSTABLE);
......@@ -194,6 +199,9 @@ namespace sensor {
Serial.print(F("Setting SCD30 timestep to "));
Serial.print(config::measurement_timestep);
Serial.println(F(" s."));
if (config::measurement_timestep < 10) {
Serial.println(F("WARNING: Timesteps shorter than 10s can lead to unreliable measurements!"));
}
scd30.setMeasurementInterval(config::measurement_timestep); // [s]
}
if ((current_state == PREPARE_CALIBRATION_UNSTABLE) || (current_state == PREPARE_CALIBRATION_STABLE)) {
......@@ -312,7 +320,12 @@ namespace sensor {
}
void calibrateSensorRightNow(int32_t calibrationLevel) {
stable_measurements = config::enough_stable_measurements;
calibrateSensorToSpecificPPM(calibrationLevel);
if (calibrationLevel >= 400 && calibrationLevel <= 2000) {
Serial.print(F("Force calibration, right now, at "));
config::co2_calibration_level = calibrationLevel;
Serial.print(config::co2_calibration_level);
Serial.println(F(" ppm."));
calibrateAndRestart();
}
}
}
......@@ -27,7 +27,9 @@
*/
// How often should measurement be performed, and displayed?
//NOTE: SCD30 timer does not seem to be very precise. Variations may occur.
//WARNING: On some sensors, measurements become very unreliable when timestep is set to 2s.
//NOTE: 10s or longer should be fine in order to get reliable results.
//NOTE: SCD30 timer does not seem to be very precise. Time variations may occur.
# define MEASUREMENT_TIMESTEP 60 // [s] Value between 2 and 1800 (range for SCD30 sensor)
// How often should measurements be appended to CSV ?
......
Markdown is supported
0% or .
You are about to add 0 people to the discussion. Proceed with caution.
Finish editing this message first!
Please register or to comment